Abstract:
Renewable energy resources play an important role with the augmentation in demand
of energy in order to fulfil the vast gap between supply power and demand power.
Microgrids play a key role in utilization of renewable energy resources. Aiming at
establishing a sustainable energy system, the number of stand-alone generation system
of PV with battery energy storage system (PV-BESS) is considerably increased around
the world. In a real grid, the implementation and analysis of PV generation system is a
very challenging task. One of the major concerns about PV power is that the change of
illumination intensity as well as the sudden variation of load changes makes the output
characteristic of PV non-linear that may lead to oscillations in dc link voltage exceeding
rated limits which in turn affecting the quality of power and stability of the grid.
Obviously, battery energy storage systems (BESSs) can be an effective solution to
smooth fluctuation and to improve the stability of the power grid. For refining the MG
stability many control approaches have been proposed for proper sharing of load. This
research work proposes Solar (PV) and Battery Energy Storage System (BESS) based
DG system in addition with robust control scheme based on the (SMC) for parallel
operating (VSI) during autonomous operation of microgrid and proportional integral
(PI) based control technique for BESS. Under different system conditions, the
efficiency of a photovoltaic (PV's) energy supply and battery energy storage network
is investigated. This research explores the system's reactions to varying solar irradiation
rates of the PV model caused by environmental conditions. Specific scenarios for
simulation are analyzed in which the system is often checked with fixed solar radiation
and changing loading conditions. The technology of (MPPT) is important due to the
reliance of PV generation on environmental conditions requiring the pv generation
system to provide its full capacity. This research deals with the Perturb and Observe
MPPT algorithm due to its quick response and less complex control circuit. For parallel
(VSI) in autonomous mode Fixed Frequency (SMVC) technique is introduced
maintains the dc link voltage oscillations, active power quality and DG system voltage
output despite sudden change in solar irradiation which causes the dc link voltage to
fluctuate. Such controller helps in improving responses of the system which include
dynamics and steady state under sudden high-power load fluctuation scenarios. Droopvii | P a g e
Integrating BESS to Mitigate the Intermittency Issues of RERs in MG
is studied in order to enable power-sharing among multiple generation systems.
Proportional Integral Control (PI) approach is adopted for Battery Energy Storage
System where the controller ensures effective tracking of dc link voltage reference
value and maintaining it with in the rated limits. Finally, the conventional proportional
integral (PI) controller with PI based BESS and the proposed SMVC with PI based
BESS is compared. The simulation results show the effectiveness and excellent control
performance of proposed control scheme in eliminating power quality issues and
maintaining stable dc link voltages. The T.H.D of output voltage for purposed control
scheme was observed to be less than 5%. Whereas, 14.50% for conventional control
scheme measured from the FFT analysis of MATLAB Simulink. The results also
validate that, in order to remove the external disturbances and to achieve response that
is robust, the suggested control technique will provide an effective solution.